Me537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality Analyzer

Product Details
Customization: Available
After-sales Service: 3 Year
Warranty: 3 Year
Still deciding? Get samples of US$ 200/Piece
Request Sample
Manufacturer/Factory & Trading Company
Gold Member Since 2021

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Plant Area
897 square meters
Management System Certification
ISO9001:2015
  • Me537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality Analyzer
  • Me537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality Analyzer
  • Me537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality Analyzer
  • Me537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality Analyzer
  • Me537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality Analyzer
  • Me537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality Analyzer
Find Similar Products

Basic Info.

Model NO.
ME537
Installation
Panel Mounting
Usage
Multi-Functional Energy Meter, Meter for Industry and Home Use, Standard Electric Energy Meter, Reactive Energy Meter, Maximum Demand Meter, Panel Analyzer
Electric Equipment
Three-phase Four-wire
Theory
Electronic Meter
Power Meter Connection
Terminal
Measured Signal
333mv CT, Rogowski Coil
Type
Power Quality Analyzer
Certification
RoHS, ISO, CE
Customized
Customized
Input Type
External CT(333mv Only), Rogowski Coil
Power
85 - 305VAC/100 - 430VDC
Storage
32 GB SD Card
Poles Description
Three Phase and Single Phase
Device Application
Power Analysis, Power Measurement, Power Quality a
Sampling Rate
8K Samples Per Second
Harmonic
50th Max
Communication
Modbus TCP, RJ45
Primary Current Range
Adjustable From 0.1A to 9999A
Voltage
Cat III 600V
Frequency Range
50/60Hz
Display Screen
3.5 Inch IPS Display
Transport Package
Poly Bag and Stand Export Carton
Specification
96*96*94mm
Trademark
MEATROL
Origin
China
HS Code
9030331000
Production Capacity
50000PCS/Year

Product Description

World-famous manufacturer
Three major production bases in Shanghai, Chongqing, and Zhejiang
Looking forward to in-depth communications, project cooperation, and exclusive agency
 Me537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality Analyzer
 
  1. Product description
ME537 three phase power quality analyzer, externally connected with open type Rogowski coil or voltage type CT, it can realize none dismantling wire test, simplify test steps, save construction cost, and is more convenient for engineering test as well as the inspection and maintenance of distribution system.
  1. Support systems of single-phase and three-phase. It can measure multiple electrical parameters such as current, voltage, power factor, power, energy, and power quality parameters including harmonic, unbalance degree, voltage swell and voltage dip, etc.
  2. In addition to the measurement function, ME537 is equipped with various records, such as waveform records and programmable interval measurement value records. To store and record data, it is internally embedded 32 GB memory card.
  3. Standard RJ45 Ethernet and RS485 communication interfaces, compatible with various configuration systems through standard Modbus TCP and Modbus RTU protocols, transmit real-time electrical parameters collected by the front-end to the system data center
    1. General parameters
Table 11 General parameters
Product name
Model No. ME537
Type Three phase power quality analyzer
Application field
Application field Power analysis, Power measurement, Power quality analysis
Wiring mode
Wiring system 3P4W_4CT
3P4W_3CT
3P3W_3CT
3P3W_2CT
1P3W
1P2w
Current sensor Rogowski coil
Voltage-output current clamp
Voltage access Direct access
Connected through voltage transformer
Storage
Type TF card
Capacity 32GB
Data export U disk export (U disk file is FAT32 system)
Communication
Interface RJ45- Ethernet RS485
Protocol Modbus-TCP Modbus-RTU
Power Supply
Power 85 - 305VAC/100 - 430VDC
Maximum power consumption 5VA
Display
Size 3.5 inch
Type IPS display
Resolution ratio 480*800
Machinery
Dimention 96*96*94mm
Weight 850g
Environment
Working environment Temperature-20ºC~+55ºC, Humidity below 90% RH
Storage environment Temperature-40ºC~+70ºC, Humidity below 95% RH(non-condensing)
Altitude ≤2km
Measurement category CAT III 600V
IP code IP30
 
    1. Measurement parameters
Table 12 Measurement parameters
Real-time measurement data
Voltage Phase voltage: Phase ABC
N phase to ground voltage
Line voltage: UAB, UBC, UCA
Voltage peak coefficient: Phase ABC
Voltage peak: Phase ABC
Current Phase current: Phase ABCN
Current peak coefficient: Phase ABC
K Factor: Phase ABC
Frequency Line frequency
Power Active power: Phase ABC and total
Reactive power: Phase ABC and total
Apparent power: Phase ABC and total
Power factor Phase ABC and total
Fundamental harmonic power factor Phase ABC and total
Electrical energy Active Energy: Phase ABC and total (import / export)
Reactive energy: Phase ABC and total (import / export)
Apparent Energy: Phase ABC and total
CO2 emissions
Harmonic measurement data
Voltage harmonics THD (Total harmonic percentage), TOHD (Odd total harmonic percentage), TEHD (Even total harmonic percentage), phase ABC 1-50th harmonic percentage, phase ABC 1-50th harmonic voltage value
Current harmonics THD (Total harmonic percentage), TOHD (Odd total harmonic percentage), TEHD (Even total harmonic percentage), phase ABC 1- 50th harmonic percentage, phase ABC 1-50th harmonic current value
Waveform
Voltage waveform Phase ABC voltage waveform or UAB, UBC, UCA line voltage waveform
Current waveform Phase ABC current waveform
Phase angle
Voltag pehase angle Phase ABC
Current pehase angle Phase ABC
Phase angle between voltage and current Phase ABC
Unbalance
Unbalance Voltage unbalance, current unbalance
Demand
Power demand and peak demand Phase ABC active power and total power, phase ABC reactive power and total power, phase ABC apparent power and total power
Current demand and peak demand Phase ABC
    1. Parameter accuracy
Table 13 Parameter accuracy
Parameter Type Description
Voltage Channel input voltage range 0-600VAC
Measurement range 0-600VAC 
Measurement accuracy 0.2%
Current Channel input voltage range 0-420mVAC
Measurement range Different current sensors have different measuring ranges
Measurement accuracy 0.2%+ Accuracy of current sensor
Frequency Measurement range 45Hz-65Hz
Measurement accuracy ±0.001Hz
Power factor Measurement range -1-+1
Measurement accuracy ±0.005
Power Active power accuracy 0.5%
Reactive power accuracy 1%
Apparent power accuracy 0.5%
Energy Active energy accuracy 0.5%
Reactive energy accuracy 1%
Apparent energy accuracy 0.5%
    1. Record storage
Table 14 Record storage
Data record
Record name Settable
Record start time Settable
Record duration Selectable
Recording interval Settable
Basic data record Phase voltage
Line voltage
Current
Frequency
Power factor
Fundamental harmonic power factor
Power(Active, Reactive, Apparent)
Active Energy (Import energy, Export energy)
Reactive energy (Import energy, Export energy)
Apparent Energy
Voltage harmonics (Total harmonic, odd total harmonic, even total harmonic)
Current harmonics (Total harmonic, odd total harmonic, even total harmonic)
Phase voltage peak
Peak factor of phase voltage
Current crest factor
Current K factor
Voltage unbalance (negative sequence, zero sequence)
Current unbalance (negative sequence, zero sequence)
Angle (phase voltage angle, phase current angle, angle between voltages, angle between currents, angle between voltages and currents)
Max min (Phase voltage, Line voltage, Current, Frequency, Power factor, Fundamental harmonic power factor, Active power, Reactive power, Apparent power)
Demand (Current, Active power, Reactive power, Apparent power)
Peak Demand (Current, Active power, Reactive power, Apparent power)
Voltage harmonic data record Voltage harmonics (Total harmonic distortion THD, Odd total harmonic TOHD, Even total harmonic TEHD, 1-50th Harmonic percentage and voltage value)
Current harmonic data record Current harmonics (total harmonic distortion THD, Odd total harmonicTOHD, Even total harmonic TEHD, 1-50th Harmonic percentage and current value)
Data storage format CSV
Event record [[1]]
Recorded data Event type
Start time
Duration
Amplitude value
Data storage format CSV
Waveform recording
Record name Settable
Record the start time Settable
Record the duration Settable
Sampling rate Settable
Logged data Phase ABC voltage waveform
Phase ABC current waveform
Data storage format CSV
  
[[1]] Event recording can only be performed when data recording is enabled.
Me537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality Analyzer

Me537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality Analyzer
Me537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality Analyzer
Me537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality AnalyzerMe537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality AnalyzerMe537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality AnalyzerMe537 Power Analyzer Rogowski Coil Modbus TCP Panel Analyzer 32GB Data Logger Power Quality Analyzer

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier