Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter

Product Details
Customization: Available
After-sales Service: 1 Year
Warranty: 1 Year
Still deciding? Get samples of US$ 29/Piece
Request Sample
Manufacturer/Factory & Trading Company
Gold Member Since 2021

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Plant Area
897 square meters
Management System Certification
ISO9001:2015
  • Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter
  • Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter
  • Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter
  • Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter
  • Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter
  • Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter
Find Similar Products

Basic Info.

Model NO.
ME237
Display
Digital
Installation
Panel Mounting
Usage
Multi-Functional Energy Meter, Meter for Industry and Home Use, Standard Electric Energy Meter, Reactive Energy Meter, Maximum Demand Meter
Electric Equipment
Three-phase Four-wire
Theory
Electronic Meter
Power Meter Connection
RS485 Interface
Measured Signal
1/5A CT, 333mv CT, Rogowski Coil
Type
Energy Meter
Certification
RoHS, ISO, CE
Customized
Customized
Optional Gateway
Ethernet Ge19, WiFi Gw19
Optional Service
Online Real Time Power Quality Monitor
Input Type
1/5A CT, 333mv CT, Rogowski Coil
Poles Description
3p3w, 3p4w
Frequency Range
50/60Hz
Application
Current,Voltage,Power,Energy,Harmonic Measurement
Display Screen
3.8 Inch LCD Segment Code Display Screen
Current Sensor Type
1/5A CT, 333mv CT, Rogowski Coil
Primary Rated Current
5A to 6ka
Secondary Rated Input
5A or 333mv or 50mv/Ka, 85mv/Ka
Voltage Range
0~600VAC
Communication
Modbus RTU, RS485 Port
Power Supply
95~265VAC/110~260VDC, 45~60Hz
Maximum Power Consumption
3.5va
Data Refresh Rate
500ms
Transport Package
Poly Bag and Stand Export Carton
Specification
8.1*8.1*3CM
Trademark
MEATROL
Origin
China
HS Code
9030331000
Production Capacity
50000PCS/Year

Product Description

Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter

Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter
1.Product description

ME237 three-phase multi-functional panel meter supports 1/5A CTs (ME237C) or external 333mV CTs (ME237V)or Flexible Rogowski coil(ME237V) .
ME237 supports 3PH3W and 3PH4W system; it can measure Current,Voltage,Power Factor,Harmonic,Power,Energy and other electrical parameters of L1,L2,L3.
The standard RS485 communication interface can be compatible with various configuration systems through the standard MODBUS-RTU protocol.
 
Description
Type 96*96 Panel Meter
Poles description 3PH3W ,3PH4W.
Application Current,Voltage,Power,Energy and harmonic measurement
display screen 3.8 inch LCD segment code display screen.
Weight 259g
Dimension L*W*D:8.1*8.1*3CM
Color White and black
Model ME237C ME237V ME237R
Current sensor type 1/5A CT 333mV CT Rogowski coil
Advantage Traditional electric meter Support to voltage output sensor and Current clamp Support to Rogowski coil directly connect without amplifier(Integrator)
Current
Model ME237C ME237V ME237R
Primary Rated current 5A to 6kA 5A 100A 200A 500A
(Accept OEM)
600A 2500A 6000A
Secondary Rated input 5A 333mV 50mV/kA 85mV/kA 50mV/kA
Input channel  maximum value 7.5A 500mV 500mV 500mV 500mV
Current measurement Range 0.005~5A 0.005~500mV 2A to 600A 2.5A to 2500A 6A to 6000A
Recommended Sensor model ACT ASCT SCT-10(10mm   5A/333mV)
SCT-16(16mm 100A/333mV)
SCT-24(24mm 200A/333mV)
SCT-36(36mm 500A/333mV)
MRC-36 NRC-150 NRC-200
Photo Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter
Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter
Voltage
Range 0~600VAC Phase to Phase Voltage
Maximum range 720VAC Phase to Phase Voltage
Digital Signal
Energy pulse output Active energy pulse output, optocoupler isolation (5kvrms)
Relay output One way electromagnetic relay output, including normally open and normally closed contacts, contact capacity: 3A 30V DC, 3A 250V AC
Digital input 2-way dry contact input, optocoupler isolation (5kvrms)
Communication
RS485 communication One way RS485 communication interface
Interface type: two wire half duplex
Communication baudrate: 2400bps ~ 19200bps
Protocol: Modbus RTU
Power supply
Power Supply 95~265VAC/110~260VDC, 45~60Hz
Maximum power consumption 3.5VA

Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter
 
 

2.Data display

Measuring data
Phase Voltage U1, U2, U3 and average value.
Line Voltage U12, U23, U31 and average value.
Current I1, I2, I3 and average value.
Power Active power,Reactive power,Apparent power (total and per phase).
Energy Active energy import,active energy export, reactive energy import, reactive energy export.apparent energy.
If it exceeds 9999999.9kwh, the energy value will be reset to "0" automatically.
Harmonic The total harmonics of each phase of voltage and current.
Power Factor Including power factor PF and fundamental power factor DPF (average value of each phase and three phases)
Grid Frequency Synthetic frequency
Update rate
Data refresh rate 500ms
Harmonic
Voltage Total harmonic phase
Current Total harmonic phase
Max / min
Voltage Per phase
Current Per phase
Power Active power,Reactive power,Apparent power (sum of all phases and three phases)
Unbalance degree
Voltage Per phase
Current Per phase
Demand / maximum demand
Current Per phase
Power Active power,  Reactive power,  Apparent power (sum of all phases and three phases)
 

3.Accuracy and certification
Note: RDG: reading value, FS: full scale
Measuring accuracy
Model ME237C ME237V ME237R
Current measurement ±0.3%RDG ±0.5%RDG ±0.5%RDG
Guarantee range of current measurement accuracy 0.5% FS~100%FS 1% FS~100%FS 2% FS~100%FS
Voltage measurement accuracy 0.2%(30~600V AC)
Grid frequency 0.01%(45~65Hz)
Power factor ±0.005
Active and apparent power IEC62053-22 level 0.5S
Reactive power IEC62053-21 level 2S
Active energy IEC62053-22 level 0.5S
Reactive energy IEC62053-21 level 2S
Environment condition
Operating temperature -25ºC~+60ºC
Storage temperature -40ºC~+85ºC
Humidity range 5~95% RH, 50ºC(non-condensing)
Class of pollution 2
Over voltage capability CAT III 1000V, It is suitable for distribution system below 277 / 480VAC
Insulation strength IEC61010-1
Altitude 3000m Max
Antipollution level IP20(Meet the standard of  IEC 60629)
Quality guarantee period 12 months
EMC(electromagnetic compatibility)
Electrostatic discharge Level CAT IV 600V (IEC61000-4-2)
Radiated immunity Level CAT III 1000V (IEC61000-4-3)
EFT Electrical fast burst immunity Level CAT IV 600V (IEC61000-4-4)
Surge immunity Level CAT IV 600V (IEC61000-4-5)
Conducted disturbance immunity Level CAT III 1000V (IEC61000-4-6)
Power frequency magnetic field immunity 0.5mT (IEC61000-4-8)
Conduction and radiation Class B (EN55022 )
Measurement standard
EN 62052-11, EN61557-12, EN 62053-21, EN 62053-22, EN 62053-23, EN 50470-1, EN 50470-3,  EN 61010-1,  EN 61010-2,  EN 61010-031

4.Connection
The meter is equipped with rich interfaces to realize different functions.
Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter
 
Point number Point type Point name Point function Remarks
1 Relay output R1 Relay normally open contact One relay output with normally open and normally closed contacts
2 R0 Relay common contact
3 R2 Relay normally closed contact
4 Pulse output POA Positive end of pulse output Active power pulse output
5 N/C N/A
6 POB Pulse output negative terminal
7 Relay output
 
DI2 Digital input channel 2 One relay output with normally open and normally closed contacts
8 DIC Digital channel common terminal
9 DI1 Digital input channel 1
10 RS485 GND RS485 communication GND RS485 communication
11 B RS485 communication B
12 A RS485 communication A
13 Power supply N Power supply(-) Range
95~265VAC/110~260VDC, 45~60Hz
14 N/C N/A
15 L Power supply(+)
16 Voltage input N N-phase voltage input Measurement voltage input channel
17 N/C N/A
18 V3 Phase C voltage input
19 N/C N/A
20 V2 Phase B voltage input
21 N/C N/A
22 V1 Phase A voltage input
23 Current input N/C N/A ME237C/ME237V/ME237R
Current channel interface.
24 N/C N/A
25 I3- Phase C current input negative
26 I3+ Phase C current input positive
27 I2- Phase B current input negative
28 I2+ Phase B current input positive
29 I1- Phase A current input negative
30 I1+ Phase A current input positive
31 RJ45 A B C three phase current input
 

4.1. Power supply

The meter adopts external power supply mode, without internal direct power supply. The power supply voltage range is 95 ~ 265VAC / 110 ~ 260VDC, 45 ~ 60Hz,  and the maximum power consumption is 3.5VA.
  • Do not connect the meter with the cable live.
  • Before connecting the power supply, make sure that the power supply voltage is within the required range, otherwise the meter can not work normally.

4.2. Voltage and current input

The meter supports two wiring modes, three-phase four wire (3P4W) and three-phase three-phase (3P3W)
  • The actual wiring mode of the meter must be consistent with that of the internal configuration of the meter.
  • Three phase four wire requires three current sensors.
  • Two or three current sensors are required for three-phase three wire system. The use of two current sensors does not affect the measurement of power and electric energy, but the current of phase B cannot be measured. Three current sensors can be used to measure phase B current.
  • The phase sequence of voltage and current must follow the phase sequence of ABC, otherwise the meter will display the phase sequence error of voltage and current.
When using the current sensor, the direction of the current arrow on the sensor must be consistent with the actual current flow direction, that is, the current arrow of the sensor points to the load end


For more information, please refer to ME237 manual. 

More additional pleasantly surprised products:

https://shpytech.en.made-in-china.com/product/RZsfXICAfYVb/China-High-Voltage-D-Src-36kv-AC-Current-Transducerrogowski-Current-Transducer.html

https://shpytech.en.made-in-china.com/product/rONaSMZGLYVc/China-Nrc-Promotion-Rogowski-Coil-Current-Transducer-Rogowski-Transducer.html

https://shpytech.en.made-in-china.com/product/qZvAEMsJHUWm/China-STP-Built-in-Integrator-Selectable-Rogowski-Coilflexible-AC-Current-Probes.html

https://shpytech.en.made-in-china.com/product/gdSTRYPJOUcW/China-Remote-Handheld-Digital-Power-Quality-Analyzer-with-TFT-Display.html

https://shpytech.en.made-in-china.com/product/mdOtRPWuHphc/China-A05-High-Quality-Shield-Aluminium-Alloy-Enclosure-5A-Output-Rogowski-Coil-Converter.html

 Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy MeterMeter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter

Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter

Meter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy MeterMeter Power Analysis Power Quality Meter Me237 Current Voltage Harmonic Measurement Energy Meter
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier