Nrc High Current Monitoring Rogowski Coil Current Sensor

Product Details
Customization: Available
Type: Rogowski
Output Signal Type: Analog Output
Still deciding? Get samples of US$ 25/Piece
Request Sample
Manufacturer/Factory & Trading Company
Gold Member Since 2021

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Plant Area
897 square meters
Management System Certification
ISO9001:2015
  • Nrc High Current Monitoring Rogowski Coil Current Sensor
  • Nrc High Current Monitoring Rogowski Coil Current Sensor
  • Nrc High Current Monitoring Rogowski Coil Current Sensor
  • Nrc High Current Monitoring Rogowski Coil Current Sensor
  • Nrc High Current Monitoring Rogowski Coil Current Sensor
  • Nrc High Current Monitoring Rogowski Coil Current Sensor
Find Similar Products

Basic Info.

Model NO.
NRC-200
Production Process
Integration
Material
Metal
Accuracy Grade
0.5G
Application
All Electronic, Electrical, Electric Related Cases
IP Rating
IP67
Certification
CE
Customized
Customized
Window Size
100, 150, 200mm
Reference Rated Current
1000A, 3000A, 6000A
Weight
Approx 140-170g
Terminal
Cold Pressed Terminal, BNC...
Coil Resistance
From 260-390Ω
Current Range(RMS)
0.5-100ka AC
Ratio
Calibrated 85mv/Ka@50Hz; 50mv/Ka@50Hz
Read Accuracy
Calibrated <0.5% (Central Position, 25ºC)
Temperature Drift
Uncalibrated 200ppm/ºC
Position Error
±1% Maximum
Output on 0A(Zero Drift)
≤0.05mv
Phase Error
≤0.5°
Linearity
±0.2% of Reading
Bandwidth
1Hz to 100kHz (-3dB)
Operating Temperature
-30ºC to 80ºC
Transport Package
Poly Bag, Standard Export Carton
Specification
Ø 8 Flexible Rogowski coil
Trademark
Meatrol
Origin
Shanghai
HS Code
8504311000
Production Capacity
50000PCS/Month

Product Description

Nrc High Current Monitoring Rogowski Coil Current Sensor
Nrc High Current Monitoring Rogowski Coil Current Sensor
 
NRC
Ø8 Flexible Rogowski coil fixed by cable ties
  1. High linearity from 1A to 100kA
  2. Wide dynamic range
  3. Very useful with large size or awkward shaped conductors or in places with limited access
  4. No danger from open-circuited secondary
  5. Not damaged by large overloads
  6. Non-intrusive, no power drawn from the main
  7. Measurement uniformity at any position of the conductor inside the coil
  8. Excellent degree of rejection to the external current conductor
Feature
NRC is a flexible current transducer based on Rogowski principle, particularly suitable for measurement in combination with portable devices. NRC coils are available in different sizes and can be supplied according to customer's design, therefore they can be used in all those applications, in which traditional transducers are not fitting due to its size and/or weight.
Due to its specific features, flexible Rogowski coil is an extremely comfortable solution for current measurement and can be used in a number of cases where traditional current transducer is not the adequate solution.
NRC coil is provided with a shield against the influence of external magnetic fields; therefore, it grants a stable measurement from low currents to hundreds of kA. The Rogowski coils must be connected to an electronic integrator for 90° phase shift compensation and frequency equalization. Our DIN-RAIL and panel meters can interface Rogowski coils directly without the need of the external integrators. This is an advantage because there are no external boxes or any power supply with consequent ease of use. The particular features of the Rogowski coils combined with the extremely flexible input programming of our portable meters, allow to carry out measurement by all applications.

 
Advantage
Calibrated to 0.5%  
8mm section easy to install
Easy to fixed on bus-bar and cable by cable ties
Lower zero drift down to 0.1mV
Related Products
S1 D1 S10 SW DA01 DA05 ME631 ME435 ME440
 
Applications
Measuring devices, lab instrumentation
Power monitoring & control systems 
Harmonics and transients monitoring
Very high current monitoring
 
What is a Rogowski coil?
Rogowski coils have been used for the detection and measurement of electric currents for decades. They are based on a simple principle: an "air-cored" coil is placed around the conductor in a toroidal fashion and the magnetic field produced by the current induces a voltage in the coil. The voltage output is proportional to the rate of change of current. This voltage is integrated, thus producing an output proportional to the current.
By using precision winding techniques, especially developed for the purpose, the coils are manufactured so that their output is not influenced by the position of the conductor within the toroid, and to reject interference from external magnetic fields caused, for example, from nearby conductors.Basically, a Rogowski coil current measuring system consists of a combination of a coil and conditioning electronics.Rogowski coil current transducers are used for the AC measurement.
They can be used in similar circumstances to current transformers but for many applications they have considerable advantages:
Wide dynamic range.
High linearity.
Very useful with large size or awkward shaped conductors or in places with limited access. Thanks to the structure without hard core, the coil can       be easily manufactured according to the application or to the available space.
Unlike traditional current transducers, there is no danger from open-circuited secondaries.
They cannot be damaged by large overloads.
They are non-intrusive. They draw no power from the main circuit carrying the current to be measured.
They are also light weighted and in some applications are light enough to be suspended on the conductor being measured.

The transducer does not measure direct currents , but unlike a current transformer, it can carry out accurate measurements of AC component even if there is a large superimposed DC component, since there is no iron core causing saturation. This feature is particularly useful for measuring ripple currents for example in battery charging systems.

Specification
MODEL NRC-100 NRC-150 NRC-200
Coil length 395mm 525mm 665mm
Window size 100mm 150mm 200mm
Reference
Rated current
1000A 3000A 6000A
Coil Resistance 260 (+/-10) Ω 320 (+/-10) Ω 390 (+/-10) Ω
Weight Approx. 140g Approx. 150g Approx. 170g
Ratio Calibrated 85mV/kA@50Hz
102mV/kA@60Hz
50mV/kA@50Hz
60mV/kA@60Hz
Uncalibrated 110mV/kA@50Hz
132mV/kA@60Hz
Read Accuracy Calibrated <0.5% (central position, 25ºC)
Uncalibrated < 5% tolerance (central position, 25ºC)
Maximum current measurable 100kA
Coil Section 8mm
Lead length 2meter
Temperature Uncalibrated 200ppm/C
Calibrated 300ppm/C
Position Error ±1% maximum
Output on 0A
(zero drift)
≤0.05mV
Phase error 0.5°
Linearity ±0.2% of reading
Bandwidth 1Hz to 100kHz(-3dB)
Operating temperature -30ºC to 80ºC
Storage temperature -40ºC to 90ºC
For other requirements, please contact us for customization.

Nrc High Current Monitoring Rogowski Coil Current Sensor
Position sensitivity
Conductor Position Typical Error (%)
Adjacent to the center of coil <0.5%
Adjacent to the inside of coil <1%


Materials
 
Coil & cable Thermoplastic rubber
flame retardant UL 94 V-0 rated
Couplings PC, ABS UL 94 V-0 rated
Color(coil) Orange, Yellow, Red, Green, Blue
Shielded 100% coil, 100% output cable

Safety
 
Certifications CE marked
Complies with
LVD EN 61010-1:2010
EMC EN 61326-1:2013
IP67
Voltage insulation Coil: 2000V
Signal cable:1000V
Safety 1000V CATIII ,600V CATIV
 
Nrc High Current Monitoring Rogowski Coil Current Sensor
Dimension's tolerance:
A,B,C,F:±5mm, D:±0.2mm,E:±10mm
Dimensions(mm) NRC-100 NRC-150 NRC-200
  1. Windows size A
135 165 210
  1. Windows size B
100 150 200
  1. Coil O.D.
151 181 226
  1. Coil section
8
  1. Lead Cable Total Length
2000
  1. Coil length
395 525 665

More Special Rogowski coil+Integrator for fault indicator
Rogowski coil NZ special for  high temperature electric furnace

Rogowski Coil Sensor for Lightning current

Safety and warning notes
In order to guarantee safe operation of the transducer and to be able to make proper use of all features and functions, please read these instructions thoroughly! Safe operation can only be guaranteed if the transducer is used for the purpose, it has been designed for and within the limits of the technical specifications. Ensure you get up-to-date technical information that can be found in the latest associated datasheet under Rogowski website.


Caution! Risk of danger
Ignoring the warnings can lead to serious injury and/or cause damage!
The electric measuring transducer may only be installed and put into operation by qualified personnel that have received an appropriate training, The corresponding national regulations shall be observed during installation and operation of the transducer and any electrical conductor. The transducer shall be used in electric/electronic equipment the respect to applicable standards and safety requirements and in accordance with all the related systems and components manufacturers' operating instructions.


Caution! Risk of electrical shock
When operating the transducer, certain parts of the module may carry hazardous live voltage (e.g., Primary conductor). The user shall ensure to take all measures necessary to protect against electrical shock. The transducer is a build-in device containing conducting parts that shall not be accessible after installation. A protective enclosure or additional insulation barrier may be necessary. Installation and maintenance shall be done with the main power supply disconnected except if there are no hazardous live parts in or in close proximity to the system and if the applicable national regulations are fully observed.

Safe and trouble-free operation of this transducer can only be guaranteed if transport, storage and installation are carried out correctly and operation and maintenance are carried out with care.


Caution! Risk of electrical shock
Do not apply around or remove from uninsulated hazardous live conductors which may result in electric shock, electric burn or arc flash.


WARING!
Do not stress the coil by applying any kind of mechanical force (transport, storage pressure, tight bending.) which will dramatically degrade the device's accuracy.



MEATROL Rogowski coil Model No. Definition:

Nrc High Current Monitoring Rogowski Coil Current Sensor
Description Connector model Window size B Signal cable length E Ratio Model No.
Calibrated
(mV/kA@50Hz)
Uncalibrated
(mV/kA@50Hz)
Ø 6 Mini type
with fixing ribbon ties
MRC 16 2m 50
(60mV/kA@60Hz)
60
(72mV/kA@60Hz)
MRC-16-2m-50
24 MRC-24-2m-50
36 MRC-36-2m-50
Ø8 Rotate bayonet type
Easy installation
with fixing ribbon ties
NRC 100 2m 85 105 NRC-100-2m-85
150 85 NRC-150-2m-85
200 50 NRC-200-2m-50
Ø12 High Voltage
36kV
D-SRC 50 2m ________ 60
(72mV/kA@60Hz)
D-SRC-50-2m-60
100 D-SRC-100-2m-60
150 D-SRC-150-2m-60
Ø12 High Sensitivity SRC 50 2m 333 360 SRC-50-2m-333
100 SRC-100-2m-333
150 SRC-150-2m-333
Ø 6 precision type TRC 16 2m 50 60 TRC-16-2m-50
24 TRC-24-2m-50
36 TRC-36-2m-50
Ø8 Snap-in type
Easy installation
ZRC 50 2m 100 / 85 / 50 105 ZRC-50-2m-85
100 ZRC-100-2m-85
150 ZRC-150-2m-85
Ø8 Spiral joint
Suitable for long term stable installation
Y-FCT B50 2m 85 110 Y-FCT-B50-2m-85
B100 85 Y-FCT-B100-2m-85
B150 85 Y-FCT-B150-2m-85
B240 50 Y-FCT-B240-2m-50
Ø8 High Frequency H-FCT B50 2m 1.2 / 6.8 / 10   H-FCT-B50-2m-10
B95   H-FCT-95-2m-10

https://shpytech.en.made-in-china.com/product/gFBazjSxhpcJ/China-STP-Lowest-Rogowski-Coil-Current-Clamp.html

https://shpytech.en.made-in-china.com/product/QFBtYorXXpWb/China-Rogowski-Coil-Handheld-Digital-Power-Quality-Analyzer-with-TFT-Display.html

https://shpytech.en.made-in-china.com/product/WwvtlOXKMmrB/China-Flexible-Rogowski-Coil-Ratio-50mv-Ka-Air-Cored-Current-Sensor-Coil-Current-Transducer.html

Nrc High Current Monitoring Rogowski Coil Current Sensor
Nrc High Current Monitoring Rogowski Coil Current Sensor
Nrc High Current Monitoring Rogowski Coil Current Sensor
Nrc High Current Monitoring Rogowski Coil Current Sensor
Nrc High Current Monitoring Rogowski Coil Current Sensor
Nrc High Current Monitoring Rogowski Coil Current Sensor

Nrc High Current Monitoring Rogowski Coil Current Sensor


 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier