Customization: | Available |
---|---|
After-sales Service: | Within 1 Year. Any Problem, We Will Send New Devic |
Warranty: | 1 Year |
Still deciding? Get samples of US$ 600/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Description | |
Model No. | MQ31 |
Type | Three-phase power quality analyzer |
Supported types of current sensor | Rogowski coil, Voltage-output current clamp |
Wiring mode | 3P4W(4CT), 3P4W(3CT), 3P3W(3CT), 3P3W(2CT), Single phase |
Storage | 16GB Micro SD card, USB DISK Download (Default storage interval: 1 minute) |
Harmonic | Simultaneous 51 times |
Application field | Power analysis, Electric energy measurement |
Display screen | 8-inch capacitive screen |
Weight | Approx 5kg |
Dimension | L*W*D:415x319x168MM |
Color | Black |
Input current | |
Primary side current range | 600A 0.5A ~ 720A 3kA 0.5A ~ 3600A 6kA 0.5A ~ 7200A |
Secondary side current range(ST08 current clamp or the same type) | 1mA~10A |
Input voltage value | 1/225mV~707mV |
Overload capacity | 2V,10s/hours |
Power supply | |
Power supply | Electricity from major loop, 90~528VAC |
Power consumption | |
Max power consumption | 15W |
Connecting terminal type | |
ABC phase current input | 3.5mm Headphone jack |
Voltage input | 4mm Banana plug |
Measurement | |
Voltage | UA, UB, UC, and average value |
Current | IA, IB, IC, IN, and average value |
Power | Active power, Reactive power, Apparent power (each phase, sum value of three phase) |
Energy | Active energy, Reactive energy, Apparent energy (each phase, sum value of three phase) Exceeds 999.9GWh, energy value automatically cleared to "0" |
Line voltage | Between phases |
Angle between line voltage | Between phases |
Angle between currents | Between phases |
Power factor | Including harmonic power factor PF and fundamental power factor DPF (each phase, average value of three phases) |
Max/Min. | |
Voltage | Each phase, average value of three phases |
Current | Each phase, average value of three phases |
Power | Active power, Reactive power, Apparent power (each phase, sum value of three phases) |
Unbalance degree | |
Voltage | Each phase, the max unbalance degree of three phases |
Current | Each phase, the max unbalance degree of three phases |
Demand/Max Demand | |
Current | Each phase, average value of three phases |
Power | Active power, Reactive power, Apparent power (each phase, sum value of three phases) |
Temperature and humidity ( Optional) | |
Temperature | 3 channels |
Humidity | 1 channel |
Power quality | |
Voltage swell | Start time, end time, amplitude value |
Voltage dip | Start time, end time, amplitude value |
Voltage harmonic value and percentage | Total harmonic, 1, 2, 3, 4...51 (51st) harmonics |
Current harmonic value and percentage | Total harmonic, 1, 2, 3, 4...51 (51st) harmonics |
General data record | |
Time interval record setting | 5~9999s (default 60s) |
Data format | .CSV |
Storage capacity | Micro SD card: 16GB |
Storage duration 3 years ( using 16GB SD card, 1 time/60s) | |
Recorded data | Basic data Voltage harmonic Current harmonic |
Event data record | |
Data fromat | .CSV |
Recorded data | Even type Start time Duration Amplitude value Voltage RMS1/2 value of each phase Voltage waveform of each phase |
Measurement accuracy | ||
Rogowski coil | Current measurement accuracy | 0.5%(1%~120% rated current), (<10A no guaranteed accuracy) |
Current gear | 600A(6A~720A): Rogowski coil TRC-36, 50mV/kA | |
3000A(10A~3600A): Rogowski coil NRC-150, 85mV/kA | ||
6000A(20A~7200A): Rogowski coil NRC-200, 50mV/kA | ||
ST08 current clamp | Current measurement accuracy | 0.5%(100mA~10A) |
1%(10mA~100mA,(<10mA no guaranteed accuracy) | ||
ABC Voltage measurement accuracy | 0.2%(5~528V AC) | |
Power factor | ±0.005 | |
Active and apparent power | IEC62053-22 Class 0.5S | |
Reactive power | IEC62053-21 Class 2S | |
Frequency | 0.01%(45~65Hz) | |
Active energy | IEC62053-22 Class 0.5S | |
Reactive energy | IEC62053-21 Class 2S | |
Environment condition | ||
Operating temperature | -25ºC~+55ºC | |
Storage temperature | -40ºC~+85ºC | |
Humidity range | 5~95% RH,50ºC(non-condensing) | |
Pollution level | 2 | |
Overvoltage capacity | III,applicable to the distribution system below 277/480VAC | |
Insulation strength | IEC61010-1 | |
Altitude | 3000m Max | |
Anti-pollution level | IP20(conforming to IEC 60629) | |
Product warranty | 24 months | |
EMC(Electromagnetic compatibility) | ||
Electrostatic discharge | Level IV(IEC61000-4-2) | |
Radiation Immunity | Level III (IEC61000-4-3) | |
EFT Electrical Fast Burst Immunity | Level IV (IEC61000-4-4) | |
Surge immunity | Level IV (IEC61000-4-5) | |
Immunity to Conducted Disturbance | Level III (IEC61000-4-6) | |
Power frequency magnetic field immunity | 0.5mT (IEC61000-4-8) | |
Conduction and Radiation | Class B (EN55022) | |
Standard compliance | ||
EN62052-11, EN61557-12, EN62053-21, EN62053-22, EN62053-23, EN50470-1, EN50470-3, EN61010-1, EN61010-2, EN61010-031 |