• Me631
  • Me631
  • Me631
  • Me631
  • Me631
  • Me631

Me631

After-sales Service: Provide Customers with Long-Term After-Sales Warra
Warranty: 1year
Transport Package: Carton
Specification: L*W*D: 96*96*99MM
Trademark: MEATROL
Origin: Shanghai China
Samples:
US$ 85/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Gold Member Since 2021

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
ME631-SD
HS Code
9030899090
Production Capacity
1000

Product Description

ME631 Three-phase Power Meter
Modbus communications overview
ME631 adopts standard protocol-Modbus-RTU. Baud rate of communication can change to 1200,2400,4800,9600 etc. through program . Error detection: CRC16 (cyclic redundancy check).

Size: The data size in Int16
Type: The encoding data type
Units: The unit of the register value
Range: The permitted values for this variable, usually a subset of what the format allows
Description: Provides information about the register and the values that applyMe631

Display
Maximum value measured
Parameter Range Resolution
Voltage 0.001V
999.9V
999.9kV
999.9MV
0.1
Current 999.9A
999.9kA
0.1
Power 999.9kW
999.9MW
0.1
Power factor 0.999 0.001
THD 99.9% 0.1%
Energy 999.9WH
999.9.KWH
999.9MWH  999.9GWH
0.1
Instantaneous rms Values
Voltage U,UTH2,UTH3,UTH4(Per Phase,AVG)
Current I,ITHD2,ITHD3,ITHD4(Per Phase,AVG)
Power P,FQ,S,PF(Per Phase,SUM)
Energy EP,EFQ,ES,Freq(Per Phase,SUM)
over 999.9GWh,value reset
UTHD(%) UTHD,THD2,THD3,THD4(Per Phase,AVG)
ITHD(%) ITHD,THD2,THD3,THD4(Per Phase,AVG)
Update rate
Data acquisition rate 400ms
Display update rate 0.5s
Energy storage interval
( prevent losing energy when power off )
10mis(default)
Calibration
Current Per phase,all
Voltage Per phase,all
Power factor Per phase,all
Energy Reset to "0"  EP,EQ,ES all phase
Record (if order please add -SD in model No.
Record interval 1s to 9999s(default 1min)
Record format csv
Record capacity 1GB(default) record 3.5years in default
Record data Voltage(V),UTHD(%),Current(A),ITHD(%),Frequency(Hz),PF(power factor),Active Power(KW),Reactive Power(KVar),Apparent Power(KVa),
ActiveEnergy(KWh),Reactive Energy(KVarh),Apparent Energy(KVah)
Communication
Transmission mode RS485 port,Half duplex
RS485 link 2 wires
Communication protocol MODBUS RTU
Settings
Communication address 1 to 247 (default 1)
Baud rate(communication speed) 1200 to 57600 baud (default 9600)
Parity Even(default),Old,None  
Data bit 8
Stop bit 1

Certificate
Environmental conditions
Operating temperature -25ºC to +55ºC
Storage temperature -40ºC to +85ºC
Humidity rating 5 to 95% RH at 50ºC(non-condensing)
Pullution degree 2
Overvoltage category III,for distribution systems up to 277/480VAC
Dielectric withstand As per IEC61010-1, Doubled insulated front panel display
Altitude 3000m Max
IP degree of protection IP20 conforming to IEC 60629
Colour White
Contractual warranty 12months
EMC
Electrostatic discharge Level IV(IEC61000-4-2)
Immunity to radiated fields Level III (IEC61000-4-3)
Immunity to fast transients Level IV (IEC61000-4-4)
Immunity to surge Level IV (IEC61000-4-5)
Conducted immunity Level III (IEC61000-4-6)
Immunity to power frequency magnetic fields 0.5mT (IEC61000-4-8)
Conducted and radiated emissions Class B (EN55022 )
Standard compliance
EN 62052-11,EN61557-12,EN 62053-21,EN 62053-22,EN 62053-23,EN 50470-1,EN 50470-3,
EN 61010-1,EN 61010-2,EN 61010-031

Specification
Measurement accuracy
 
Current 0.5% from 1% to 120%(don't ensure accuracy when <10A)
Rated current 500A(0.5% from 10A to 600A)
3000A(0.5% from 30A to 3600A)
10kA(0.5% from 100A to 12kA)
Rogwoski coil specification 85mV/kA@50Hz±0.5%
Voltage 0.2% from 100V to 500V(L-L and L-N)
Power factor ±0.005 from 10% to 120%
Active/Apparent Power IEC62053-22 Class 0.5
Reactive power IEC62053-21 Class 2
Frequency 0.01% from 45 to 65Hz
Active energy IEC62053-22 Class 0.5s
Reactive energy IEC62053-21 Class 2
Measurement arrange
Measured voltage 100V to 500V AC
Frequency range 50/60Hz
Input-current characteristics
Primary current range Adjustable from 0.1A to 9999A
Measurement input range 1/225mV-333mV
Permissible overload 600mV for 10s/hours
Control Power
AC/DC 85 to 265V AC/DC, 3W
Output
Digital output 1×digital output(2 ports)(controlled by Modbus)
2.5kVrms insulation
Maximum Switching Power :
10A, 277VAC
10A, 28VDC
Wire diameter for terminals
Connections-terminals Screw terminals 2.5mm2,interval 5.08mm
Alarm
Setting U and I Each phase
Output form Buzzer,Relay
 Me631










 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Gold Member Since 2021

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Plant Area
897 square meters
Management System Certification
ISO9001:2015