Customization: | Available |
---|---|
After-sales Service: | Any Problem, We Will Send 1PCS New for Replacement |
Warranty: | 1 Years |
Still deciding? Get samples of US$ 100/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Specification | |||
Model | ME531 | ||
Product component type | Multifunction power meter | ||
Poles description | 3PH4W 3PH3W 1PH2W (L-N); 1PH2W(L-L);1PH3W(L-L-N) |
||
Device application | Power analysis Energy meter |
||
Input type | External CT(333mV only) And External Rogowski coil |
||
Display | None Display | ||
Sampling rate | 8k samples per second | ||
Mounting mode | DIN RAIL | ||
Harmonic | 52th Max | ||
Mechanical characteristics | |||
Weight | 125g | ||
Dimension | L*W*D:122*87*23mm |
Instantaneous rms Values | |
Voltage | U,UTH2,UTH3,UTH4(Per Phase, AVG) |
Current | I,ITHD2,ITHD3,ITHD4(Per Phase, AVG) |
Power | P,Q,S,PF(Per Phase, SUM) |
Energy | EP, EQ, ES, Freq (Per Phase, SUM) over 1.0 xkWh,value reset |
UTHD(%) | UTHD,THD2,THD3,THD4(Per Phase, AVG) |
ITHD(%) | ITHD,THD2,THD3,THD4(Per Phase, AVG) |
PF | PFa, PFb, PFc, AVG |
Update rate | |
Data acquisition rate | 400ms |
Calibration | |
Current | Per phase, all |
Voltage | Per phase, all |
Power factor | Per phase ,all |
Energy | Reset to "0" EP,EQ,ES all phase |
Communication | |
Transmission mode | RS485 port,Half duplex |
RS485 link | 3 wires |
Communication protocol | MODBUS RTU |
Settings | |
Communication address | 1 to 247 (default 1) |
Baud rate(communication speed) | 1200 to 57600 baud (default 19200) |
Parity | None (default),Old, Even |
Data bit | 8 |
Stop bit | 1 |
Environmental conditions | ||
Operating temperature | -25ºC to +55ºC | |
Storage temperature | -40ºC to +85ºC | |
Humidity rating | 5 to 95% RH at 50ºC(non-condensing) | |
Pullution degree | 2 | |
Overvoltage category | III,for distribution systems up to 277/480VAC | |
Dielectric withstand | As per IEC61010-1, Doubled insulated front panel display | |
Altitude | 3000m Max | |
IP degree of protection | IP20 conforming to IEC 60629 | |
Colour | White | |
Contractual warranty | 12months | |
EMC | ||
Electrostatic discharge | Level IV(IEC61000-4-2) | |
Immunity to radiated fields | Level III (IEC61000-4-3) | |
Immunity to fast transients | Level IV (IEC61000-4-4) | |
Immunity to surge | Level IV (IEC61000-4-5) | |
Conducted immunity | Level III (IEC61000-4-6) | |
Immunity to power frequency magnetic fields | 0.5mT (IEC61000-4-8) | |
Conducted and radiated emissions | Class B (EN55022 ) | |
Standard compliance | ||
EN 62052-11,EN61557-12,EN 62053-21,EN 62053-22,EN 62053-23,EN 50470-1,EN 50470-3, EN 61010-1,EN 61010-2,EN 61010-031 |
Measurement accuracy | ||
Current | 0.5% from 1% to 120%(don't ensure accuracy when <10A) | |
Rated current (5 level selectable) | 100A(0.5% from 10A to 120A) 600A(0.5% from 10A to 720A) 1000A(0.5% from 10A to 1200A) 3000A(0.5% from 30A to 3600A) 6000A(0.5% from 60A to 7200A) |
|
Rogwoski coil connect setting | 100A | MRC-16 |
600A | MRC-36 | |
1000A | Y-FCT-200 or Y-FCT-350 or NRC-100 | |
3000A | NRC-150 or Y-FCT-510 | |
6000A | NRC-200 or Y-FCT-800 | |
Voltage | 0.2% from 80V to 400V(or 100 to 500V) | |
Power factor | ±0.005 from 10% to 120% | |
Active/Apparent Power | IEC62053-22 Class 0.5 | |
Reactive power | IEC62053-21 Class 2 | |
Frequency | 0.01% from 45 to 65Hz | |
Active energy | IEC62053-22 Class 0.5s | |
Reactive energy | IEC62053-21 Class 2 |
Measurement arrange | |
Measured voltage | 80V to 400V AC(or 100 to 500V) |
Frequency range | 50/60Hz |
Input-current characteristics | |
Primary current range | Adjustable from 0.1A to 9999A |
Measurement input range | 1/225mV-333mV |
Permissible overload | 600mV for 10s/hours |
Power | |
AC/DC | 24VDC |
Output | |
Relay | 1×digital output(2 ports) from 1pcs relay,rated 24V/800mA, 75mΩmax, 2.5kVrms insulation(controlled by Modbus) Maximum Switching Power : 0.5A, 125VAC 1A, 30VDC |
Opticalcoupler | Max voltage :80VDC;Max current 50mA Recommend Current :10mA |
Wire diameter for terminals | |
Connections-terminals | Screw terminals 2.5mm2,interval 5.08mm |
Alarm | |
Setting | U and I Each phase,AVG |
Output form | Relay |