Still deciding? Get samples of $ !
Request Sample
|
| Customization: | Available |
|---|---|
| Type: | Rogowski |
| Output Signal Type: | Analog Output |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
TRC
| MODEL | TRC-16 | TRC-24 | TRC-36 | |
| Coil length | 80mm | 97mm | 130mm | |
| Window size | 16mm | 24mm | 36mm | |
| Reference Rated current |
100A | 300A | 600A | |
| Weight | Approx 80-100g | |||
| Coil Resistance | from 100 to 300 Ω | |||
| Maximum current measurable | 100kA | |||
| Coil Section | 6mm | |||
| Lead length | 2meter | |||
| Output (di/dt) | Uncalibrated | 60mV/kA@50Hz 72mV/kA@60Hz | ||
| Calibrated | 50mV/kA@50Hz 60mV/kA@60Hz | |||
| Read Accuracy | Calibrated <0.5% (central position, 25ºC) Uncalibrated < 5% tolerance (central position, 25ºC) |
|||
| Temperature | Uncalibrated 200ppm/C | |||
| Calibrated 300ppm/C | ||||
| Position Error | ±1% maximum | |||
| Output on 0A (zero drift) | ≤0.05mV | |||
| Phase error | ≤0.5° | |||
| Linearity | ±0.2% of reading | |||
| Bandwidth | 1Hz to 100kHz(-3dB) | |||
| Operating temperature | -30ºC to 80ºC | |||
| Storage temperature | -40ºC to 90ºC | |||
| Other requirements, please contact us to OEM. | ||||
| Coil & cable | Thermoplastic rubber flame retardant UL 94 V-0 rated |
| Couplings | PA6 UL 94 V-O rated |
| Color(coil) | Black, Yellow, Red, Green, Blue |
| Shielded | 100% coil, 100% output cable |
| Certifications | CE marked |
| Complies with LVD EN 61010-1:2010 EMC EN 61326-1:2013 |
|
| IP68 | |
| Voltage insulation | Coil: 1000V |
| Signal cable:1000V | |
| Safety | 1000V CATIII ,600V CATIV |

| Dimensions(mm) | TRC-16 | TRC-24 | TRC-36 |
| A.Windows size A | 22 | 27.5 | 36 |
| B.Windows size B | 16 | 24 | 37 |
| C.Coil O.D. | 34 | 39.5 | 48 |
| D.Coil section | 6 | ||
| E.Lead Cable Total Length | 2000 | ||
| F:Coil length | 80 | 97 | 130 |